Prismatic LiFePO4 cells, integrated into TOBOR-engineered packs, racks and containers. Fourteen 314 Ah cells make a 44.8 V pack; 252 make an 806.4 V rack; twenty racks fill a 5.06 MWh CTX container. Commercial MTX systems from 30 kW run on the 100 Ah cell.
LiFePO4 · 3.2 V · 314 Ah
Pack · 14S1P · 44.8 V
Rack · 252S1P · 253.2 kWh
Container · 20 racks · 5.06 MWh
The 250 kW–10 MW range is built on one LFP cell, 3.2 V · 314 Ah, wired in series into TOBOR-engineered packs and racks. Each CTX rack carries its own 125 kW PCS module and is managed by the in-house TOBOR BMS.
PTX systems (250 kW–2 MW) use the same 314 Ah cell on an 819.2 V nominal DC platform, one to eight strings in parallel. *Cycle figures are catalogue values; the project offer confirms the supplied configuration.
Commercial cabinets need modest, runtime-sized energy; utility containers need the most energy per rack. We match the cell to the job.
Phones and EVs use NMC because energy density matters more than cycle life. A stationary battery cycling daily in Indian summer needs cycle life and thermal stability first.
LFP chemistry is far more thermally stable than NMC. In May heat, that margin — plus liquid cooling in CTX containers — keeps the system clear of thermal runaway.
~6,000 cycles on the 100 Ah platform and ~8,000 on 314 Ah, versus NMC's typical 2,000–3,000. Lower cost per delivered kWh for arbitrage and peak shaving.
Iron and phosphate chemistry. No cobalt supply-chain exposure, and a simpler end-of-life story for stationary storage.
From a 30 kW commercial cabinet to a 10 MW utility block — here's what's inside.
Commercial cabinets for MSMEs, clinics and hotels. Battery energy is sized to the backup duration you need.
819.2 V strings: 257 kWh at 250 kW up to 2.06 MWh at 2 MW for factories, campuses and HT consumers.
20 racks of 252 cells in one 20 ft liquid-cooled container — 5.06 MWh with a 125 kW PCS per rack.
Four containers, 80 racks, 20.26 MWh behind a 33 kV RMU — for utilities, DISCOMs and IPPs.
Tell us your power, duration and site conditions. We'll respond within 48 hours with the cell platform, rack count and container layout — and can quote packs, racks or spares for TOBOR systems and integrators.